Global Switch Technical Specification Amsterdam East

AMSTERDAM EAST

Location – The data centre is located 2km from the financial district and city centre – A local Metro station is immediately outside the main gate – S chiphol International Airport is 10 minutes away by car Building Overview – G lobal Switch has a long term ground lease with automatic renewal rights – Purpose built – W ill exceed Tier III operational performance – 3 2,000 sq m of gross space – 2 data floors – Flexible IT space with ability to create bespoke environments as required Main Structural Features – S tructural steel frame with reinforced concrete floors and metal faced cladding – 6 m slab to slab height – N o raised floor – M inimum from finish floor: 3.9m clear height to underside of deepest beam

Cooling – 3 5MW of cooling provision – M inimum N+2 resilience on all systems – C hiller Assist free-cooling – Fan wall units control temperature and humidity in technical space within the recommended range of ASHRAE TC9.9 Security – O perations Centre manned 24x7x365 – S ecurity guard patrols 24x7x365 – C ontinuous CCTV surveillance of external and internal areas – C CTV records kept for 31 days – C omprehensive intruder detection and alarms to all areas – P erimeter Intrusion Detection system (PIDs) – S trict access control procedures to ISO 27001 – A ccess control using proximity card readers and biometric systems – P hysical access via mantrap – S ecure managed delivery and loading area available 24x7x365

Fire Detection and Suppression – Fully addressable fire detection system in all areas – A spirated early warning smoke detection system (monitored 24x7x365) – G as suppression system in technical areas Critical Environments Management – E xperienced 24x7x365 facilities management team – Environment (thermal conditions) monitored 24x7x365 – A ll Building Management Systems (BMS) monitored 24x7x365 – C omprehensive energy metering systems – Internationally recognised critical environments programme

Other Services – Cross connects – Customer reports – D eliveries and storage – D esign and build – Fit out – On-site facilities – Remote hands – Technical cleaning – Waste disposal

Connectivity – C arrier and cloud neutral

– Floor loading of 15kN/m² – 2 goods lifts (4 tonnes)

– N etwork dense with access to multiple global and regional carriers and Internet service providers offering Dark Fibre, Wavelength, Ethernet, MPLS, VPLS, IP Transit, Peering, CDN, Storage, Virtualised Services (SDN), Voice and Mobile Services – A ccess to multiple cloud services through leading public, private and hybrid cloud solution providers – 3 diverse MMRs servicing the campus – 3 diverse Building Entry Points servicing the campus – D iverse cable routes and pathways – C ampus fibre system interconnecting Amsterdam East to Amsterdam West – R oof space availability for satellite and antennae equipment – A MS-IX, NL-IX, GE-CIX, NetIX Communications and Speed-IX present

Power – 5 0kV utility supply – U tility power supply capacity of 40MVA (planned) – Technical (IT) Power supplied by on-site Static UPS N+1 redundancy – M echanical systems backed up by standby generators with N+1 redundancy – Fully diverse power distribution to technical areas – O n-site fuel storage to support 24 hours at full load with 24x7x365 fuel delivery – O ffering 2,000 W/m 2 as standard, with higher power density solutions fully supported

Certifications – ISO 9001, 14001, 27001, 45001, 50001 – ISAE 3402 – AMS-IX – P CI DSS Compliant

Technical specification, which is subject to change, relates to the completion of all stages of Global Switch Amsterdam East

Global Switch Amsterdam East Johan Huizingalaan 759 1066 VH Amsterdam Netherlands +31 20 6666 300 salesamsterdam@globalswitch.com

Powered by