Global Switch Singapore Woodlands Brochure

TECHNICAL SPECIFICATION

Critical Environments Management – Experienced 24x7x365 facilities management team – Environmental (thermal conditions) monitored 24x7x365 – All Building Management Systems (BMS) monitored 24x7x365 – Comprehensive energy metering system – Internationally recognised critical environments programme

Connectivity – Carrier and cloud neutral – Network dense with access to multiple global and regional carriers and Internet service providers offering Dark Fibre, Wavelength, Ethernet, MPLS, VPLS, IP Transit, Peering, CDN, Storage, Virtualised Services (SDN), Voice and Mobile Services – Access to multiple cloud services through leading public, private and hybrid cloud solution providers

Cooling – 28.8MW of installed cooling provision – Minimum N+1 resilience on all systems – CRAH units control temperature and humidity in technical space within the recommended range of ASHRAE TC9.9 – Diverse distribution pipework throughout – Chilled water cooling system Security – Operations Centre manned 24x7x365 – Security guard patrols 24x7x365 – Continuous CCTV surveillance of external and internal areas – CCTV records kept for 90 days – Comprehensive intruder detection and alarms to all areas – Perimeter Intrusion Detection system (PIDs) – Strict access control procedures to ISO 27001 – Access control using proximity card readers and biometric systems – Physical access via mantrap – Secure managed delivery and loading area available 24x7x365 – Compliant with Monetary Authority of Singapore’s (MAS) TVRA requirements

Main Structural Features – Reinforced concrete frame with reinforced concrete floors, concrete walls with external metal cladding – 5.4m slab to slab height – Raised floor height of 900mm – Minimum height from raised floor: 3.5m clear to underside of ceiling – Floor loading of 15N/m² – 1 goods lift (5 tonnes), 3 passenger lifts Power – 22kV utility supply with N+N redundancy – Utility power supply capacity of 30MVA (current) – Technical (IT) power and mechanical systems supplied by on-site Diesel Rotary UPS with N+2 and N+1 redundancy respectively – Fully diverse power distribution to technical areas – On-site fuel storage to support 24 hours at full capacity with 24x7x365 fuel delivery – Offering 1,500W/m² as standard, with higher power density solutions fully supported

– 2 dedicated Meet Me Rooms – 4 diverse building entry points – Diverse cable routes and pathways – Roof space availability for satellite and antennae equipment

Other Services – Cross connects – Customer reports – Deliveries and storage – Design and build – Fit-out – On-site facilities – Remote hands – Technical cleaning – Waste disposal

Fire Detection and Suppression – Analogue addressable fire detection system in all areas – Aspirated early warning smoke detection system (monitored 24x7x365) – Inert gas suppression system in technical areas with dry pipe pre-action sprinkler system for additional resiliency

Certifications – ISO 9001, 14001, 27001, 45001, 50001